Electronic Engine Control
Main Features:
There are four Models under ATS520 series.
ATS 520: Dual power intelligent switch module.
ATS 520I: Based on ATS 520, it adds power measurement function.
ATS 520R: Based on ATS 520, it adds RS485 port.
ATS 520IR: Based on ATS 520, it adds power measurement function and RS485 port.
*Dual core 32bit high performance single chip microcomputer. 3.5inch screen, Available in Chinese/English languages, user's language setif necessary.
*System type can set as: "S1 Mains S2 Mains", "S1 Mains, S2 Gen", "S1 Gen S2
Mains", "S1 GenS2 Gen".
*Acrylic material is adapted to protect the screen. PC material panel, waterproof, oil-proof, UV-resistant, good operation feel and
long service life.
*USB Port: parameters can be set even without power through USD port to monitor
in real time.
*With RS485 communication port, can achieve "Three Remote" functions via
MODBUS protocol.
*S1 / S2 independent overcurrent warning or trip alarm function. *Collection and display, gen, mains, power, phase and other parameters.
*Display S1/S2 Total kW Energy, Total KVAR Energy, Total Close Times.
*For Stored-Energy type ATS, its close relay will active after the PF Input is active.
*The genset can be Manual Test on site to achieve start/stop operation.
*ATS Controller has function of automatic Re-closing.
*Applicable for PC Three-stage, PC Two-stage, CB and CC switch. *Applicable for 2 isolated neutral line.
*Real-time clock (RTC); Event log Function (Event log can record 14 items circularly).
*Automatic/Manual mode. In manual mode, can force the switch to close or open.
*Can control two generators to work as Cycle Run mode, Master Run mode and Balance Run mode.
*Suitable for various AC systems (3 phase 4-wires, 3-phase 3-wires, single-phase
2-wire, and 2-phase 3-wire).
*Input/output function, status can be shown directly.
*Real time clock inside.
*Totally 8 relays output, 6 relays function configurable.
*Totally 6 configurable switch input, 4 switch function configurable. *Control Protection: Realize automatic ATS switching of generator sets, perfect fault display and protection functions.
*Standard water-proof rubber gasket. The waterproof can IP54. *Module design: All the connections are adapted with European connectors so that installation, connection, repair and replacement can be more easily.