1. If not, access to port 0 and communication sport, the power supply will not be damaged if invested
2. If the power supply is not connected, the communication sport must be able to resist the mass, B-ZU-MASA, 30 V between A and B, and the Sport 485 communication should not be damaged after 10 seconds
3. If the current turns on, the voltage from a to mass of 30 V, B+ 30 V is against the dough and the voltage between A and B 30 V against the dough and cannot be damaged after 10 seconds of pressure
4. Technical plastic material has high mechanical strength, good heat and good electric insulation
5. The analog extension plate has a stable structure, excellent performance and a long service life
Technical data:
Article Type: Analog Extension Card
Model: WS-ADDS
Material: Technical Plastic
Supply Voltage (V):
Current Work (MA): 50 ~ 230
4. Description Door:
4.1 Initial Sport Analogy:
4.1.1 Output voltage: 0 ~ 10 V ± 5 %
4.12 Initial voltage: 0 V
4.2 Analogy entry sports:
4.2.1 0 '10 V Admission:
A. prevented 250k
B. Voltage -0.7 ~ 15V
4.2.2 0'20ma input:
A. Prevention 250Q
B. Electricity: 0''25MA
4.3 Temperature measurement connection PT100:
4.3.1 Divided into 3 connections:
A PV, combined with a single line connection PT100
B.P, connect one of the compensation lines to C.PG and connect the other compensation line
4.3.2 After the connection is normal, you can read the correct temperature information
4.3.3 The viewing temperature with an open circuit is approximately 265 (television failure). )
4.4 Formal Temperature Measurement Connection K-K-K Term Fuel: Measurement connection:
4.4.1 The mass cannot be connected
4.4.2 Divided into k+ and k-
4.4.3 The inactive tension to the earth is approx. 1.3 V, and the 444 interval is +-39 mv
4.4.5 Short -Circuit to show the current ambient temperature (corresponds to a temperature difference within 0)
4.4.6 The temperature increase can be seen if the thermocouple is connected to heating
4.4.7 Insecure output when floating
6 Description Communication:
6.1 In the initial state, station number 1 and the transmission rate is 04 (9600)
6.2 The parameters can be restored on the circuit board by means
6.3 Send hexadecimal to the beginning extension: 01040000001A71C1 You can read the data throughout the buffer (16 -bit data per record). )
6.4 The returned data are as follows:
6.4.1 01 04 34 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 E7 01 20 FF F7 00 24 00 04 B8
6.4.2 0 ~ 7 These are analogous initial data data
6.4.3 8 ~ 15 are input data buffets
6.4.4 16 ~ 19 are the thermal temperature data of the fuel
6.4.5 20 ~ 23 They are PT100 temperature data buffer
6.4.6 24 is the cache number of the station number
6.4725 is the Baudio rat parameter buffer
6.5 PT100 Verification: Close the three interfaces PT100 and enter the command "01 06 00 68 11 55 C4 79" To perform the PT100 check. The module does not respond.
6.6 Change the analog output
Example: Change a single analog output
Station Number/Function Code/Address H/Address L/Data H/Data L/RedundanzPrüfcode H/Redundanztefrüode L
01 06 00 00 00 89 ca
Put the first analog output at 0 V - Data/1000 is the real initial value of the analog
Example: Change several analog outputs
Station Number/Function Code/Home Address H/Start of Address L/Quantity h/Quant
01 10 00 00 02 04 00 10 00 F3 A6
Place the first and second analog output at 0.016 V - Bytes = Dex2 Number
List of packaging:
1 x -Analog expansion card
1 x User Manual
1