Current Sensors
standard:
IEC6044-1, EN60044-1, VDE0414-44-1, GB1208-2006
Technical indicators:
parameters
Mechanical parameters
frequency
50/60 Hz
case
PC/UL94-V0
Rated input
15A-300A
Spool
Polybutylene terephthalate
Measuring range
5%In-120%In
nuclear
Silicon Steel
Rated output
1A, 5A
Internal structure
Tighten
Rated voltage
0.72KV (AC)
Operating temperature
-25-+75
Dielectric strength
3.0KV/1mA/1min
Working humidity
85%
Insulation resistance
DC500V/100Mmin
Output Connections
terminal
Technical data
type
Ratio (A)
Burden (VA) Level: 1.0
frequency
DM-20
15/5A (1A)
1.5(5T)
50/60
20/5A (1A)
2.5(5T)
50/60
25/5A (1A)
2.5(4T)
50/60
30/5A (1A)
2.5(4T)
50/60
40/5A (1A)
2.5(3T)
50/60
50/5A (1A)
2.5(2T)
50/60
60/5A (1A)
1.5
50/60
75/5A (1A)
1.5
50/60
80/5A (1A)
1.5
50/60
100/5A (1A)
2.5
50/60
125/5A (1A)
2.5
50/60
150/5A (1A)
2.5
50/60
200/5A (1A)
3.75
50/60
250/5A (1A)
3.75
50/60
300/5A (1A)
3.75
50/60