Features: The QFM2100 duct sensors are for use in air ducts of ventilation and air conditioning plant for acquiring: The relative humidity, and temperature | The sensors are used as: Control sensors in the supply or extract air | Reference sensors, e.g. for shifting the dew point
Limit sensors, e.g. in connection with steam humidifiers | Limit sensors, e.g. for measured value indication or for connection to a building automation and control system | Sensors for enthalpy and absolute humidity, together with SEZ220
Measurement Range Humidity: 0 to 95% RH | Measurement Accuracy: Humidity at 30 to 70% RH and 23°C: ±3% RH | Temperature, at 15°C to 35°C: ±0.8K | Temperature, at 35°C to 50°C: ±1.0K | Operating Voltage: AC 24V, DC 13.5 to 35V | Time constant: Humidity: <20 s, Temperature in with 2 m/s moved air: <3.5 min
Analog Output, Signal: DC 0 to 10V, DC 4 to 20 mA | Signal Output Humidity: DC 0 to 10V | Immersion Length: 90 to 154 mm | Connection, Electrical: Screw Terminals | Type of Fixing: Flange | Degree of Protection: IP 54
Supply Scope: 1 Unit of QFM2100 Duct Sensor, 1 unit of Screw Set, Instruction Manual | Applications: Storage and production facilities in the paper, Texttile, Pharmaceutical,Food, Chemical, Electronics Industry, Laboratories, Hospitals, Computer and EDP Centres.
وصف
QFM2100 Duct Sensor acquires the relative humidity in the air duct via its capacitive humidity sensing element whose electrical capacitance changes as a function of the relative humidity. This sensor acquires the temperature in the air duct via its sensing element whose electrical resistance changes as a function of the temperature.