Current:continuous 4A dc, intermittent 6A for 10 secs
Resistance:15 ohms minimum
REGULATION:+/- 1.0%
THERMAL DRIFT:0.04% per deg. C change in AVR ambient
وصف
SENSING INPUT
Voltage:190-264V ac
Frequency:50-61 Hz nominal
phase:1
Wire:2
OUTPUT
Voltage:max 90V dc at 207V ac input
Current:continuous 4A dc, intermittent 6A for 10 secs
Resistance:15 ohms minimum
REGULATION:+/- 1.0%
THERMAL DRIFT:0.04% per deg. C change in AVR ambient
TYPICAL SYSTEM
RESPONSE
AVR response:20ms
Filed current to 90%:80 mS
Machine Volts to 97%:300 mS
EXTERNAL VOLTAGE
ADJUSTMENT:+/-10% with 1 k ohm 1 watt trimmer
UNDER FREQUENCY
PROTECTION
Set point:95% Hz
Slope:170% down to 30 Hz
UNIT POWER DISSIPATION:12 watts maximum
BUILD UP VOLTAGE:4 Volts @ AVR terminals
ANALOGUE INPUT
Maximum input:+/- 5 Vdc
Sensitivity:1v for 5%
Input resistance:1k ohm
QUADRATURE DROOP INPUT
10 ohms burden
Max. sensitivity: 0.07 A for 5% droop 0PF
Max. input: 0.33A
ENVIRONMENTAL
Vibration
20-100 Hz,50mm/se
100Hz - 2kHz, 3.3g
Operating temperature
-40 to +70 Deg. C
Relative Humidity 0-70
Deg. C
95%
Storage temperature
-55 to +80 Deg. C