Electronic Engine Control
HAT530N Dual-channel power supply automatic switching controller With microprocessor as the core, it can accurately detect two three-phase voltages and two single-phase voltages, make accurate judgments on voltage abnormalities (power loss, overvoltage, undervoltage, overfrequency, underfrequency, phase loss, reverse phase sequence), and control ATS switching after delay. It is suitable for controlling a disconnected position and non-disconnecting ATS switch, and the controller has the function of sending a signal to start the generator set after the abnormal delay of a power supply. Through the LINK port communication, the "three remote" functions of telemetry, remote signaling and remote control can be realized.
Performance and characteristics
Collect two three-phase voltages and frequencies;
One way, two ways
Line voltage Uab, Ubc, Uca Line voltage Uab, Ubc, Uca
Phase voltage Ua,Ub,Uc Phase voltage Ua,Ub,Uc
Frequency Hz Frequency Hz
It has the functions of over-voltage, under-voltage, phase loss, reverse phase sequence, over-frequency and under-frequency detection, among which the reverse phase sequence, over-frequency and under-frequency detection functions are set to not enable at the , and the user can set them according to their needs;
The operating parameters of the controller can be set through the upper computer test software, and when used, the LINK port of the controller is connected to the upper computer with SG72 interface module (USB to LINK) or other conversion modules;
The normal delay of 1# power supply or 2# power supply can be set (range 0~60 seconds). The starting delay of the generator set can be set (range 0~3600 seconds);
The abnormal delay of 1# power supply or 2# power supply can be set (range 0~60 seconds). The shutdown delay of the generator set can be set (range 0~3600 seconds);
Through the panel buttons, you can set parameters such as "1# power main", "2# power main", "mutual backup", "automatic/manual" to achieve 1# power supply main, 2# power supply mains or mutual standby power supply;
The closing output can be set to pulse or continuous output;
Two-way N-line separation design;
It is equipped with automatic/manual state switching, and in manual mode, the switch can be switched through the panel buttons;
The panel LED can clearly display the working status of the switch;
It is designed with a forced breaking input port, and when the input port is valid, the forced switch is forced to the breaking position (only effective for the ATS switch with breaking position);
Programmable relays (AUX.OUTPUT1, AUX. OUTPUT2) It can control the power supply switching of ATS working power;
The output contact capacity of 1# and 2# power switching relays (1# CLOSE, 2# CLOSE, OPEN) is 5A AC250V, all of which are passive contacts, which can be directly used to drive switch conversion, etc.;
The output contact capacity of the genset starting relay (GENS START) is 7A AC250V /7A DC28V, which is a passive normally closed contact